《直流系统蓄电池充放电试验报告.docx》由会员分享,可在线阅读,更多相关《直流系统蓄电池充放电试验报告.docx(9页珍藏版)》请在课桌文档上搜索。
1、直流蓄电池充放电试验检查报告批准:审查:校核:编写:检查日期:报告编写日期:工作负责人:工作班成员:*公司20*年*月*日试验项目营地直流蓄电池充放电试验页次试验部门电气二次安装部位营地IOKV配电室1/5蓄电池组别测量仪器名I称型号仪器编号测量环境万用表FLUKEl15C温度26.3智能型蓄电池放电仪BFD220R20湿度60%红外线点温枪雷泰试验日期2011.08.23-、放电记录放电时间(三)12345678910电流(八)20202020202020202020电压(V)211.3210.1208.7207.1205.4203.5201.5199.0195.6192.5编号初始值(V)
2、(V)(V)(V)(V)(V)(V)(V)(V)(V)12.1632.0032.0232.0091.9931.9771.9611.9421.9191.8921.87022.1652.0322.0222.0081.9911.9761.9591.9401.9171.8891.86732.1632.0352.0252.0111.9951.9791.9631.9441.9211.8931.87042.1652.0312.0202.0061.9881.9721.9551.9351.9101.8801.85552.1632.0382.0302.0182.0031.9891.9741.9561.9361.9
3、131.89562.1732.0392.0302.0172.0011.9871.9711.9521.9301.9061.86672.1652.0412.0332.0222.0071.9941.9801.9631.9441.9231.90682.1732.0382.0282.0141.9971.9831.9661.9461.9241.8991.87892.1662.0372.0282.0162.0011.9871.9721.9541.9331.9101.892102.1662.0392.0312.0192.0041.9901.9751.9581.9381.9151.898112.1632.042
4、2.0352.0252.0122.0011.9891.9741.9581.9401.926122.1642.0382.0292.0172.0021.9891.9731.9551.9351.9111.893132.1622.0312.0192.0051.9871.9701.9531.9321.9071.8761.850142.1652.0432.0362.0262.0122.0001.9861.9711.9541.9351.921152.1652.0412.0342.0222.0081.9941.9801.9641.9451.9241.908162.1692.0362.0242.0101.992
5、1.9761.9591.9391.9151.9871.864172.1642.0402.0322.0202.0061.9921.9771.9611.9421.9211.905182.1572.0292.0172.0021.9851.9681.9511.9301.9051.8751.849192.1602.0372.0292.0162.0001.9861.9701.9531.9321.9071.888202.1612.0382.0292.0162.0011.9861.9711.9541.9331.9081.889212.1642.0382.0282.0141.9981.9841.9671.947
6、1.9241.8981.876222.1612.0412.0342.0232.0101.9971.9831.9671.9491.9301.916232.1582.0292.0162.0011.9831.9671,9481.9261.8991.8661.837242.1602.0382.0302.0182.0031.9901.9751.9581.9381.9161.898252.1602.0322.0232.0101.9941.9801.9641.9441.9221.8961.876262.1632.0382.0302.0182.0031.9891.9741.9561.9351.9121.893
7、272.1662.0422.0362.0252.0122.0001.9861.9701.9531.9341.920282.1622.0372.0292.0162.0011.9871.9711.9531.9331.9101.891292.1582.0322.0292.0091.9921.9771.9601.9411.9181.8911.869302.1652.0412.0342.0232.0091.9961.9821.9671.9491.9281.913试验项目营地直流蓄电池充放电试验页次试验部门电气二次安装部位营地IoKV配电室2/5蓄电池组另I测量仪器名称型号仪器编号测量环境万用表FLUKE
8、l15C温度26.3智能型蓄电池放电仪BFD220R20湿度60%红外线点温枪雷泰试验日期2011.08.23一、放电记录放电时间(三)12345678910电流(八)20202020202020202020电压(V)211.3210.1208.7207.1205.4203.5201.5199.0195.6192.5编号初始值(V)(V)(V)(V)(V)(V)(V)(V)(V)(V)312.1622.0402.0322.0202.0051.9921.9771.9611.9411.9191.902322.1672.0362.0272.0131.9971.9821.9661.9481.9261.
9、9011.881332.1572.0342.0242.0111.9961.9801.9641.9461.9241.8981.878342.1682.0422.0342.0212.0071.9921.9771.9601.9401.9171.900352.1702.0452.0372.0252.0111.9981.9831.9671.9491.9281.912362.1622.0412.0332.0222.0081.9941.9801.9641.9461.9251.909372.1632.0412.0342.0222.0081.9961.9801.9641.9441.9231.907382.163
10、2.0382.0282.0162.0001.9871.9701.9521.9311.9071.888392.1592.0382.0292.0162.0001.9861.9691.9501.9281.9041.883402.1632.0422.0352.0242.0101.9991.9841.9681.9501.9301.915412.1642.0372.0272.0131.9971.9831.9651.9461.9231.8961.874422.1572.0402.0312.0192.0041.9911.9751.9581.9371.9151.897432.1652.0382.0272.012
11、1.9961.9811.9631.9421.9181.8901.866442.1532.0302.0192.0041.9871.9721.9531.9321.9051.8751.847452.1582.0362.0252.0111.9951.9791.9621.9441.9201.8921.869462.1642.0442.0372.0262.0121.9991.9841.9691.9501.9301.905472.1592.0342.0232.0091.9931.9771.9591.9411.9171.8891.866482.1642.0362.0252.0111.9951.9781.961
12、1.9421.9191.8961.869492.1532.0302.0192.0041.9871.9701.9521.9321.9071.8761.849502.1622.0382.0282.0162.0011.9851.9601.9511.9301.9051.885512.1542.0352.0252.0111.9961.9801.9641.9461.9231.8971.876522.1582.0382.0282.0162.0011.9861.9701.9531.9311.9071.888532.1622.0412.0322.0192.0041.9911.9741.9561.9361.913
13、1.895542.1592.0402.0312.0192.0041.9911.9751.9571.9371.9141.896552.1632.0392.0312.0192.0041.9911.9741.9571.9361.9131.894562.1582.0402.0322.0212.0071.9941.9781.9611.9421.9201.903572.1562.0312.0202.0061.9891.9741.9551.9341.9081.8781.850582.1572.0382.0292.0172.0021.9891.9731.9551.9351.9121.894592.1562.0
14、312.0182.0031.9851.9691.9491.9271.9001.8681.838602.1622.0312.0192.0041.9881.9731.9541.9331.9081.8781.852试验项目营地直流蓄电池充放电试验页次试验部门电气二次安装部位营地IOKV配电室3/5蓄电池组别测量仪器名称型号仪器编号测量环境万用表FLUKE115C温度26.3智能型蓄电池放电仪BFD220R20湿度60%红外线点温枪雷泰试验日期2011.08.23、放电记录放电时间(三)12345678910电流(八)20202020202020202020电压(V)211.3210.1208.720
15、7.1205.4203.5201.5199.0195.6192.5编号初始值(V)(V)(V)(V)(V)(V)(V)(V)(V)(V)612.1582.0342.0242.0101.9951.9781.9611.9431.9201.8931.872622.1582.0232.0091.9931.9761.9571.9371.9151.8861.8491.816632.1652.0412.0312.0182.0041.9881.9721.9561.9351.9121.895642.1552.0322.0222.0091.9941.9781.9611.9441.9211.8951.874652.
16、1582.0302.0172.0011.9851.9661.9451.9241.8951.8571.823662.1552.0322.0202.0061.9901.9731.9551.9361.9111.8811.857672.1662.0372.0252.0111.9961.9781.9601.9411.9181.8901.867682.1572.0292.0172.0011.9851.9661.9461.9251.8981.8651.826692.1562.0332.0222.0081.9911.9781.9581.9381.9141.8861.862702.1592.0302.0172.
17、0031.9851.9701.9491.9281.9071.8691.840712.1572.0372.0262.0131.9971.9831.9641.9451.9211.8941.871722.1532.0292.0172.0031.9851.9711.9501.9291.9031.8711.842732.1592.0342.0022.0071.9901.9751.9541.9331.9081.8771.851742.1592.0402.0302.0172.0011.9881.9701.9511.9301.9051.884752.1472.0262.0081.9961.9781.9591.
18、9321.9111.8991.8761.846762.1632.0402.0302.0161.9991.9871.9681.9491.9271.9021.882772.1572.0282.0141.9971.9801.9611.9401.9191.8981.8851.852782.1612.0352.0232.0071.9921.9731.7541.9351.9091.8781.852792.1592.0252.0101.9931.9761.9551.9331.9111.8801.8401.805802.1572.0322.0202.0051.9901.9721.9531.9351.9101.
19、8811.875812.1552.0292.0172.0011.9851.9661.9471.9271.9001.8671.805822.1532.0202.0091.9911.9721.9581.9231.9021.8861.8511.823832.1552.0322.0192.0041.9891.9701.9511.9311.9051.8731.864842.1562.0372.0262.0121.9991.9821.9641.9461.9241.8971.875852.1602.0302.0141.9971.9761.9601.9521.9201.9001.8801.850862.152
20、2.0362.0252.0131.9971.9841.9651.9471.9241.8991.871872.1532.0352.0242.0111.9941.9811.9611.9421.9181.8911.867882.1522.0332.0222.0081.9921.9781.9591.9401.9161.8891.866892.1602.0372.0272.0141.9971.9841.9651.9461.9231.8961.874902.1502.0312.0192.0061.9891.9751.9551.9361.9181.8821.857试验项目营地直流蓄电池充放电试验页次试验部门
21、电气二次安装部位营地IOKV配电室4/5蓄电池组别测量仪器名称型号仪器编号测量环境万用表FLUKEl15C温度26.3智能型蓄电池放电仪BFD220R20湿度60%红外线点温枪雷泰试验口期201108.23、放电记录放电时间(三)12345678910电流(八)20202020202020202020电压(V)211.3210.1208.7207.1205.4203.5201.5199.0195.6192.5编号初始值(V)(V)(V)(V)(V(V)(V)(V)(V)(V)912.1572.0342.0232.0101.9931.9801.9601.9411.9171.8901.866922
22、.1582.0352.0242.0101.9931.9801.9591.9391.9141.8661.859932.1672.0372.0262.0111.9971.9801.9621.9451.9231.8961.875942.1542.0292.0162.0001.9851.9661.9451.9261.8991.8661.837952.1632.0432.0342.0212.0081.9921.9751.9601.9411.9181.902962.1552.0292.0162.0011.9861.9671.9471.9291.9031.8701.856972.1532.0262.0131
23、.9961.9811.9611.9391.9191.8911.8561.842982.1582.0161.9961.9741.9531.9271.8981.8701.8581.8371.815992.1562.0352.0232.0091.9951.9771.9581.9411.9181.8911.8681002.1522.0262.0131.9971.9821.9621.9411.9211.8941.8601.8301012.1552.0202.0051.9881.9711.9481.9251.9051.8901.8371.8051022.1552.0312.0192.0031.9891.9
24、701.9501.9311.9051.8741.8471032.1472.0171.9971.9761.9561.9301.9071.8861.8491.8251.8021042.1532.0302.0172.0011.9861.9661.9451.9251.8971.8611.828最高电压2.1732.0442.0372.0262.0122.0011.9891.9741.9541.9401.926最低电压2.1472.0161.9961.9741.9531.9271.8981.8701.8491.8251.802蓄电池温度27.527.527.527.627.627.627.727.727
25、.727.727.7室内环境温度26.326.827.127.527.828.428.3628.327.827.527.2试验项目营地直流蓄电池充放电试牙佥页次试验部门维护部电气二次安装部位营地IOKV配电室5/5蓄电池组别测量仪器名称型号仪器编号测量环境万用表FLUKEl15C温度26.3智能型蓄电池放电仪BFD220R20湿度60%红外线点温枪雷泰试验日期201108.23、充电记录充电时间(三)进线正温度()进线负温度(C)最高温度()环境温度(C)127.430.133.527.7227.029.032.927.0326.029.233.227.6427.329.233.227.652
26、6.929.833.126.3625.629.632.126.8726.929.532.325.7827.929.133.026.5928.429.033.125.91028.231.133.826.51128.331.333.725.91228.231.033.526.0营地直流蓄电池组放电试验由2011/08/2309:00:00开始进行,至2011/08/2319:00:00完毕,放电电流为20A,放电时间10小时,蓄电池组各放电数据正常,电池温升正常,计算蓄电池组容量为195.6AH,达到额定容量200AH的97.80%,满足其技术条件和运行要求。充电试验由2011/08/2319:10:00开始进行,至2011/08/2407:10:00完毕,蓄电池电压223.7V、电流0.0A,蓄电池组各充电数据正常,电池温升正常,设备运行正常。试验结论:该组蓄电池充放电试验合格。(合格或不合格)